S0005036
Zhendre WIC-WIF Combi split type 40m3
Zhendre Walk-in type, combined cold & freezer room, split type, 40m3 for
storage of vaccines at national and sub-national levels.
Indicative Price 44,766.81 USD
General description:
Zhendre Walk-in type combined cold & freezer room, split type, 40m3 for storage of vaccines at national and sub-national levels.
Cold Room (25 m2):
External dimensions: L=3650 x W=3500 x H=2775 mm
Internal dimensions: L=3200 x W=3200 x H=2415 mm
Freezer Room (15 m2):
External dimensions: L=2300 x W=3500 x H=2775 mm
Internal dimensions: L=2000 x W=3200 x H=2415 mm
1. Technical specifications:
Prefabricated Walk-in type, combined cold & freezer room walk-in, split type, supplied with all necessary mechanical and electrical fittings and equipment for quick and easy installation in the field.
The unit is designed to operate from a mains supply of 400V/3/50Hz as standard or 220V/3/60Hz as an option, with a dual refrigeration unit, each refrigeration unit is sized to give 100% stand-by capacity designed to operate in a maximum ambient of 43°C. Units operating from a different mains supply than described above can be supplied as option, please confirm the power rating during the time of ordering.
The complete unit is also designed for installation in a housed area such as a warehouse in order to meet temperature design standards and to protect the equipment from elements.
1.1 Specification details:
Prefabricated modular combined cold & freezer room complete with floor, wall and ceiling panels.
Refrigeration unit (WIC):
-uses CFC-free refrigerant gas R134a, compliant with the requirements of the Montreal Protocol.
Refrigeration unit (WIF):
-uses CFC-free refrigerant gas R452a, compliant with the requirements of the Montreal Protocol.
Both Refrigeration units:
-have an automatic duty sharing with a time relay to balance their wear
-are fitted with run-hour meters.
-with sealants for air tightening the cut outs between pipes and wall panel.
-refrigeration systems shall be complete with copper tubing, electrical cabling and necessary fittings to cover a distance of 20 meters between condensers and the evaporators.
Temperature control:
The thermostat is calibrated to ITS-90 and accuracy is ± 0.5°C.
Internal temperature (WIC): +2°C to +8°C adjustable.
Internal temperature (WIF): -20°C
Panel Insulation:
Foam blowing agent with low GWP (for WIF only): HFO (HydroFluoro-Olefin)
Insulation thickness (WIF): 150 mm with U-value of 0.17 W/m2K
Insulation thickness (WIC): 100 mm with U-value of 0.223 W/m2K
Wall and roof panel construction:
Panels are self-supporting, wall and roof panel are made from smooth galvanized metal plate 5/10ths with polyester lacquer 25µm.
Floor construction:
Top of floor panel is coated with hard-wearing non-slip finish.
Door construction:
Doors are constructed and insulated to the same standard as applicable for wall panels.
Opening width (WIC): 1000mm
Opening width (WIF): 1000mm
Opening height: 2200mm
Door frame heating element (for WIF only).
With heavy duty hinges and lock with internal safety release.
An internal plastic strip curtain.
Shelving:
Free-standing, adjustable shelving units, made from Anodized Aluminum.
Shelves have 470mm depth, 5 levels
Alarm System:
A mains-operated audible and visible alarm in the event of mains failure or when room temperatures are outside set limits.
Thermometer:
A gas pressure thermometer with capillary tube & reversible flange, complying with PQS E006/TH02.
Voltage Stabilizer:
Bundled with a voltage stabilizer suitable for the cold room power requirement.
Remote Temperature Monitoring System (Optional):
Remote Temperature Monitoring System RTMS – Optional/ to be supplied upon request.
Overall dimensions:
Individual components will be able to fit through an 800mm wide door opening (with the door leaf removed if necessary).
Warranty:
To be covered by a 2 year warranty in the event of any component failure arising from defective design, materials or workmanship.
Instructions:
Assembly, operation, technical drawings, wiring diagrams, maintenance and repair manuals in English shall be provided. Upon request, instructions shall be in one of the UN languages most appropriate to the installation site: Arabic, French, Mandarin Chinese, Russian or Spanish.
Shipping Information:
Estimated shipping weight: 2700 Kg
Estimated Shipping volume: 32 m3
Material safety data sheet information (MSDS):
UN Code: UN3159
Danger Class: 2.2
Packing instruction: P200
Instructions: T50
Proper shipping name: 1.1.1.2 Tetrafluoroethane; refrigerant gas R134A
Related Products